Comment: The following text has been provided for project engineers. The text can be copied from this page and pasted into your word processor for inclusion in system specifications.

SLX 130 Engineering Specifications

A submersible level transmitter shall be provided to sense the liquid level of the _____________ at the location as shown on the plan drawings and in accordance with the manufacturer’s recommendations.

The transducer housing shall be fabricated of PVC with a 2.5” diameter Teflon diaphragm. Silicone oil shall be used as a hydraulic fill. The sensor shall be mounted using its signal cable and have 3/4” NPT pipe threading for pipe mounting.

The internal air pressure of the sensor assembly shall be relieved to atmospheric pressure through a sealed breather system.

USE ONLY ONE OF THE FOLLOWING SECITONS:

M Version - 4-20 mA Output

The transmitter shall be a 4-20 mADC, 2 wire, 10-30 VDC loop-powered type, with its output signal directly proportional to the measured level excursion. The transducer shall be a CONTEGRA Model SLX 130-M.

MIS Verion - 4-20 mA Output Intrinsically Safe Version

The transmitter shall be a 4-20 mADC, 2 wire, 10-30 VDC loop-powered type, with its output signal directly proportional to the measured level excursion. The sensor shall be UL 913 approved intrinsically safe. The transducer shall be a CONTEGRA Model SLX 130-MIS.

E Version - 0.5-4.5 VDC Output

The transmitter shall be a 3 wire, 5 VDC powered type with an output of 0.5-4.5 V directly proportional to the measured level excursion. The transducer shall be UL Listed. The transducer shall be a CONTEGRA Model SLX 130-E.

EIS - 0.5-4.5 VDC Output Intrinsically Safe

The transmitter shall be a 3 wire, 5 VDC powered type with an output of 0.5-4.5 V directly proportional to the measured level excursion. The sensor shall be UL 913 approved intrinsically safe. The transducer shall be a CONTEGRA Model SLX 130-E.